DIN Rail Mount Energy Meter with Pulse Outputs.
DIN Rail Mount Energy Meter with Pulse Outputs.
Discontinued!
This product has been discontinued and is no longer available. There is no direct replacement. Don't worry, we have some options to help you find what you need:
Visit our Electricity category for similar products.
Or let's do a search and help you find what you need:
Features
Applications
| Inputs | |
| AC Control Power | 50/60 Hz; 5 VA maximum; 90 V minute; UL maximums: 600 V L-L (347 V L-N); CE maximums: 300 V L-N (520 V L-L) |
| DC Control Power | 3W maximum; UL and CE: 125 to 300 VDC (external DC current limiting required) |
| Voltage Input | UL: 90 V L-N to 600 V L-L CE: 90 V L-N to 300 V L-L |
| Current Input Scaling | 5 A to 32,000 A |
| Input Range | 0 to 0.333 V or 0 to 1 V (selectable) |
| Accuracy | |
| Real Power and Energy | 0.5% (ANSI C12.20, IEC 62053-22 Class 0.5 S) |
| Outputs | |
| Real Energy Pulse | N.O. Static |
| Alarm Contacts | N.C. Static |
| Mechanical | |
| Mounting | DIN Rail or 3-point screw mount, NEMA 4 enclosure optional |
| Environmental | |
| Operating Temperature Range | -30 to 70°C (-22 to 158°F) |
| Storage Temperature Range | -40 to 85°C (-40 to 185°F) |
| Humidity Range | <95% Relative Humidity, Non-Condensing |
| Inputs | |
| AC Control Power | 50/60 Hz; 5 VA maximum; 90 V minute; UL maximums: 600 V L-L (347 V L-N); CE maximums: 300 V L-N (520 V L-L) |
| DC Control Power | 3W maximum; UL and CE: 125 to 300 VDC (external DC current limiting required) |
| Voltage Input | UL: 90 V L-N to 600 V L-L CE: 90 V L-N to 300 V L-L |
| Current Input Scaling | 5 A to 32,000 A |
| Input Range | 0 to 0.333 V or 0 to 1 V (selectable) |
| Accuracy | |
| Real Power and Energy | 0.5% (ANSI C12.20, IEC 62053-22 Class 0.5 S) |
| Outputs | |
| Real Energy Pulse | N.O. Static |
| Alarm Contacts | N.C. Static |
| Mechanical | |
| Mounting | DIN Rail or 3-point screw mount, NEMA 4 enclosure optional |
| Environmental | |
| Operating Temperature Range | -30 to 70°C (-22 to 158°F) |
| Storage Temperature Range | -40 to 85°C (-40 to 185°F) |
| Humidity Range | <95% Relative Humidity, Non-Condensing |