With 240 V AC Supply, 240 V AC Power & 2x Relay O/P, this temperature panel meter is used for multi-zone temperature monitoring and thermocouple and rtd monitoring. It has display of 4-digit, 7-segment LED; red, 0.83" (21 mm).
With 240 V AC Supply, 240 V AC Power & 2x Relay O/P, this temperature panel meter is used for multi-zone temperature monitoring and thermocouple and rtd monitoring. It has display of 4-digit, 7-segment LED; red, 0.83" (21 mm).
The DP606A/DP612A Display Meter offers a flexible, easy to use 6 or 12 zone, 4 digit temperature and process measurement solution in a rugged 1/4 DIN Aluminum housing. Selectable configuration eliminates the need for jumpers. The DP606A supports 6 independent zones (3 wire RTD limited to 6 zones on all models).
The DP606A and DP612A Series is our newest line of affordable multi-channel panel meters. These models offer increased accuracy, wider operating temperatures and increased flexibility over the CN606 and CN612 models that they replace.
All zones are scanned at a 400 ms rate. The display shows the reading of each zone sequentially. High and low Alarms with SPDT relay outputs are available for monitoring and alarm purposes.
The input, power and communications are also now isolated allowing for easier deployment and more reliable operation. The rugged extruded aluminum 1/4 DIN case combines with the improved isolation to provide an extremely durable product.
These meters can read up to 12 sensors and include user selectable RS232 or RS485 communications using Modbus(R). Two user configurable Alarm relays are standard on all models.
The universal input allows user selection between thermocouple (9 types), RTD 2-wire, RTD 3-wire, 4 to 20 mA and 1000 mV input options. These input selections are firmware selectable through the front panel buttons or Modbus serial commands.
Note: While the inputs are universal and can be changed via firmware (no dip switches), all 6 or 12 inputs on a given unit must be set to the same type of input for operation.
Features
Applications
| Series | DP606A Series |
| No. of zones | 6 or 12 (RTD 3 wire 6 channels for all models) |
| Type | temperature panel meter |
| Display | 15 mm 7-segment LED |
| Supply voltage | 240 V AC Supply |
| Display time | 1 to 99 s |
| Output type | 240 V AC Power & 2x Relay O/P |
| Scan time | 400 ms |
| Display | 4-digit, 7-segment LED; red, 0.83" (21 mm) |
| Input types | TC: J, K, T, E, R, S, B, C, N RTD: 2 or 3 wire (PT100, 0.00385; CU10, 0.00427; NI120, 0.00672) Process: 4 to 20 mA, 0 to 1 V |
| Input Types | 9 thermocouple types (J, K, T, E, R, S, B, C, and N), 2 or 3 wire RTDs (Pt 100, Ni 120, Cu 10), DC voltage (0-1 V DC), or DC current (0 to 24 mA) |
| Resolution | 1°, 1 mV, 0.01 mA |
| Number of Zones | 6 independent zones (3 wire RTD limited to 6 zones) |
| ADC | 24-bit Sigma Delta |
| Scan Rate | 400 ms |
| Communications | RS232 and RS485 (user selectable) up to 115.2k baud, Modbus protocol (RTU) |
| Line Voltage/Power | 120/240 V AC, 50/60 Hz, 3 W maximum |
| Isolation per 1 min, power to alarm relay | 2.3k Vac (3.2k Vdc) |
| Low-Voltage/Power Option | 9 to 36 V DC, 3 W maximum |
| Isolation per 1 min, power to serial | 2.3k Vac (3.2k Vdc) |
| Communications | Selectable RS232 / RS485, Modbus RTU |
| Isolation per 1 min, input to serial | 500 Vac (720 Vdc) |
| Protection | NEMA-1/Type 1 front bezel |
| Alarm relays | De-energizes on alarm; latching or non-latching; high, low or hi/low |
| Process Voltage Accuracy | ± 1 mV (0 to 1000 mV) |
| Operating temp | -4 to 158°F (-20 to 70°C) |
| Process Current Accuracy | ± 10 μA (0 to 24.00 mA) |
| Storage temp | -40 to 185°F (-40 to 85°C) |
| Panel Cutout | 1/4 DIN, 3.62 x 3.62" (92 x 92 mm) |
| Panel cutout | 1/4 DIN 3.6 x 3.6" (92 x 92 mm) |
| Pollution Degree | 2 |
| Min rear panel depth | 5.5" (140 mm) |
| Altitude | Up to 2000 meters |
| ECCN | EAR99 |
| Alarm Relays AC Power Option | 2x SPDT, 240 V AC, 5 A Load |
| Safety | 2014/35/EU |
| Alarm Relays DC Power Option | 2x SPDT, 36 V DC, 3 A Load |
| EMC | 2014/30/EU |
| Operating Environmental Conditions | -4 to 158°F (-20 to 70°C), 90% RH non-condensing |
| RoHS | 2011/65/EU |
| Storage Environmental Conditions | -40 to 185°F (-40 to 85°C), 90% RH non-condensing |
| UL file no. | E209855, UL/cUL Listed |
| Input Accuracy, Type J | -238 to 32°F (-150 to 0°C) ±1.0°C (25°C); 32 to 2192°F (0 to 1200°C) ±1.0°C |
| Power | AC |
| Input Accuracy, Type K | -238 to 32°F (-150 to 0°C) ±1.0°C (25°C); 32 to -2438°F (0 to -1372°C) ±1.0°C (CHROMEGA-ALOMEGA) |
| Zones | 6 |
| Input Accuracy, Type T | -238 to 32°F (-150 to 0°C) ±1.0°C (25°C); 32 to 752°F (0 to 400°C) ±1.0°C (Copper-Constantan) |
| Input power | 120/240 Vac; 50/60 Hz, 3 watts maximum |
| Input Accuracy, Type E | -238 to 32°F (-150 to 0°C) ±1.0°C (25°C); 32 to 1832°F (0 to 1000°C) ±1.0°C (CHROMEGA-Constantan) |
| Isolation per 1 min, power to input | 2.3k Vac (3.2k Vdc) |
| Input Accuracy, Type R | -58 to 32°F (-50 to 0°C) ±1.0°C (25°C); 32 to 3250°F (0 to 1788°C) ±1.0°C (Pt/13%Rh-Pt) |
| Alarm relays rating | 240 Vac max, 5A max load |
| Input Accuracy, Type S | -58 to 32°F (-50 to 0°C) ±1.0°C (25°C); 32 to 3214°F (0 to 1768°C) ±1.0°C (Pt/10%Rh-Pt) |
| Dimensions | 3.7 x 3.7 x 5.3" (95 L x 95 W x 135 Dia mm) |
| Input Accuracy, Type B | 302 to 1292°F (150 to 700°C) ±1.0°C (25°C); 1292 to 3308°F (700 to 1820°C) ±1.0°C (30%Rh-Pt/6%Rh-Pt) |
| Weight | 26 oz (725 g) |
| Input Accuracy, Type C | 5%Re-W/26%Re-W 32 to 4208°F (0 to 2320°C) ±1.0°C (25°C) |
| Input Accuracy, Type N | -238 to 32°F (-150 to 0°C) ±1.0°C (25°C); 32 to 2372°F (0 to 1300°C) ±1.0°C (Nicrosil-Nisil) |
| Input Accuracy, RTD Pt | Pt, 0.00385, 100 Ω, 2/3 Wire, -328 to 1562°F (-200 to 850°C) ±1.0°C |
| Input Accuracy, RTD Cu | Cu, 0.00427, 10 Ω, 2/3 Wire, -328 to 500°F (-200 to 260°C) ±1.0°C |
| Input Accuracy, RTD Ni | Ni, 0.00672, 120 Ω, 2/3 Wire, -112 to 500°F (-80 to 260°C) ±1.0°C |
| Absolute Maximum Input | 3.3 V (Process Voltage) or 30mA (Process Current) |
| External Fuse Required | Time-Delay UL 248-14 listed: 25 mA/250 V, 300 mA/250 V (Low-Voltage Option); Time-Lag IEC 127-3 recognized: 25 mA/250 V, 300 mA/250 V (Low-Voltage Option) |
| Environmental Conditions (Operating) | -20 to +70°C (-4 to +158°F), 90% RH non-condensing |
| Environmental Conditions (Storage) | -40 to +85°C (-40 to +185°F), 90% RH non-condensing |
| Serial Configuration | Default RS485, 115.2k baud, no Parity; baud rates 4800/9600/19200/38400/57600/115200; parity None/Odd/Even |
| Modbus Address | 1 to 247 (default 1) |
| Scan Time | Default 3 seconds |
| Wiring | Copper conductors only, minimum 20 AWG, UL Rated; insulation rated for at least 185°F (85°C) and 600 V; torque all connections to 0.5-5.31 in-lb (0.6 Nm) |
| Approvals | EMC: 2014/30/EU; LVD: 2014/35/EU; UL 61010-1 / CSA C22.2 NO. 61010-1-12; UL 61010-2-201 / CSA C22.2 NO. 61010-2-201:14; UL File Number E209855; WEEE 2012/19/EU |
| Dimensions | 3.74 x 3.74 x 5.31" (95 x 95 x 135 mm) |
| Weight | 1.6 lbs (725 g) |
| Series | DP606A Series |
| No. of zones | 6 or 12 (RTD 3 wire 6 channels for all models) |
| Type | temperature panel meter |
| Display | 15 mm 7-segment LED |
| Supply voltage | 240 V AC Supply |
| Display time | 1 to 99 s |
| Output type | 240 V AC Power & 2x Relay O/P |
| Scan time | 400 ms |
| Display | 4-digit, 7-segment LED; red, 0.83" (21 mm) |
| Input types | TC: J, K, T, E, R, S, B, C, N RTD: 2 or 3 wire (PT100, 0.00385; CU10, 0.00427; NI120, 0.00672) Process: 4 to 20 mA, 0 to 1 V |
| Input Types | 9 thermocouple types (J, K, T, E, R, S, B, C, and N), 2 or 3 wire RTDs (Pt 100, Ni 120, Cu 10), DC voltage (0-1 V DC), or DC current (0 to 24 mA) |
| Resolution | 1°, 1 mV, 0.01 mA |
| Number of Zones | 6 independent zones (3 wire RTD limited to 6 zones) |
| ADC | 24-bit Sigma Delta |
| Scan Rate | 400 ms |
| Communications | RS232 and RS485 (user selectable) up to 115.2k baud, Modbus protocol (RTU) |
| Line Voltage/Power | 120/240 V AC, 50/60 Hz, 3 W maximum |
| Isolation per 1 min, power to alarm relay | 2.3k Vac (3.2k Vdc) |
| Low-Voltage/Power Option | 9 to 36 V DC, 3 W maximum |
| Isolation per 1 min, power to serial | 2.3k Vac (3.2k Vdc) |
| Communications | Selectable RS232 / RS485, Modbus RTU |
| Isolation per 1 min, input to serial | 500 Vac (720 Vdc) |
| Protection | NEMA-1/Type 1 front bezel |
| Alarm relays | De-energizes on alarm; latching or non-latching; high, low or hi/low |
| Process Voltage Accuracy | ± 1 mV (0 to 1000 mV) |
| Operating temp | -4 to 158°F (-20 to 70°C) |
| Process Current Accuracy | ± 10 μA (0 to 24.00 mA) |
| Storage temp | -40 to 185°F (-40 to 85°C) |
| Panel Cutout | 1/4 DIN, 3.62 x 3.62" (92 x 92 mm) |
| Panel cutout | 1/4 DIN 3.6 x 3.6" (92 x 92 mm) |
| Pollution Degree | 2 |
| Min rear panel depth | 5.5" (140 mm) |
| Altitude | Up to 2000 meters |
| ECCN | EAR99 |
| Alarm Relays AC Power Option | 2x SPDT, 240 V AC, 5 A Load |
| Safety | 2014/35/EU |
| Alarm Relays DC Power Option | 2x SPDT, 36 V DC, 3 A Load |
| EMC | 2014/30/EU |
| Operating Environmental Conditions | -4 to 158°F (-20 to 70°C), 90% RH non-condensing |
| RoHS | 2011/65/EU |
| Storage Environmental Conditions | -40 to 185°F (-40 to 85°C), 90% RH non-condensing |
| UL file no. | E209855, UL/cUL Listed |
| Input Accuracy, Type J | -238 to 32°F (-150 to 0°C) ±1.0°C (25°C); 32 to 2192°F (0 to 1200°C) ±1.0°C |
| Power | AC |
| Input Accuracy, Type K | -238 to 32°F (-150 to 0°C) ±1.0°C (25°C); 32 to -2438°F (0 to -1372°C) ±1.0°C (CHROMEGA-ALOMEGA) |
| Zones | 6 |
| Input Accuracy, Type T | -238 to 32°F (-150 to 0°C) ±1.0°C (25°C); 32 to 752°F (0 to 400°C) ±1.0°C (Copper-Constantan) |
| Input power | 120/240 Vac; 50/60 Hz, 3 watts maximum |
| Input Accuracy, Type E | -238 to 32°F (-150 to 0°C) ±1.0°C (25°C); 32 to 1832°F (0 to 1000°C) ±1.0°C (CHROMEGA-Constantan) |
| Isolation per 1 min, power to input | 2.3k Vac (3.2k Vdc) |
| Input Accuracy, Type R | -58 to 32°F (-50 to 0°C) ±1.0°C (25°C); 32 to 3250°F (0 to 1788°C) ±1.0°C (Pt/13%Rh-Pt) |
| Alarm relays rating | 240 Vac max, 5A max load |
| Input Accuracy, Type S | -58 to 32°F (-50 to 0°C) ±1.0°C (25°C); 32 to 3214°F (0 to 1768°C) ±1.0°C (Pt/10%Rh-Pt) |
| Dimensions | 3.7 x 3.7 x 5.3" (95 L x 95 W x 135 Dia mm) |
| Input Accuracy, Type B | 302 to 1292°F (150 to 700°C) ±1.0°C (25°C); 1292 to 3308°F (700 to 1820°C) ±1.0°C (30%Rh-Pt/6%Rh-Pt) |
| Weight | 26 oz (725 g) |
| Input Accuracy, Type C | 5%Re-W/26%Re-W 32 to 4208°F (0 to 2320°C) ±1.0°C (25°C) |
| Input Accuracy, Type N | -238 to 32°F (-150 to 0°C) ±1.0°C (25°C); 32 to 2372°F (0 to 1300°C) ±1.0°C (Nicrosil-Nisil) |
| Input Accuracy, RTD Pt | Pt, 0.00385, 100 Ω, 2/3 Wire, -328 to 1562°F (-200 to 850°C) ±1.0°C |
| Input Accuracy, RTD Cu | Cu, 0.00427, 10 Ω, 2/3 Wire, -328 to 500°F (-200 to 260°C) ±1.0°C |
| Input Accuracy, RTD Ni | Ni, 0.00672, 120 Ω, 2/3 Wire, -112 to 500°F (-80 to 260°C) ±1.0°C |
| Absolute Maximum Input | 3.3 V (Process Voltage) or 30mA (Process Current) |
| External Fuse Required | Time-Delay UL 248-14 listed: 25 mA/250 V, 300 mA/250 V (Low-Voltage Option); Time-Lag IEC 127-3 recognized: 25 mA/250 V, 300 mA/250 V (Low-Voltage Option) |
| Environmental Conditions (Operating) | -20 to +70°C (-4 to +158°F), 90% RH non-condensing |
| Environmental Conditions (Storage) | -40 to +85°C (-40 to +185°F), 90% RH non-condensing |
| Serial Configuration | Default RS485, 115.2k baud, no Parity; baud rates 4800/9600/19200/38400/57600/115200; parity None/Odd/Even |
| Modbus Address | 1 to 247 (default 1) |
| Scan Time | Default 3 seconds |
| Wiring | Copper conductors only, minimum 20 AWG, UL Rated; insulation rated for at least 185°F (85°C) and 600 V; torque all connections to 0.5-5.31 in-lb (0.6 Nm) |
| Approvals | EMC: 2014/30/EU; LVD: 2014/35/EU; UL 61010-1 / CSA C22.2 NO. 61010-1-12; UL 61010-2-201 / CSA C22.2 NO. 61010-2-201:14; UL File Number E209855; WEEE 2012/19/EU |
| Dimensions | 3.74 x 3.74 x 5.31" (95 x 95 x 135 mm) |
| Weight | 1.6 lbs (725 g) |