Analog/Digital 5kV Megger; 500, 1000, 2500, 5000V; 15 Tohms; Cat IV 600V.
Analog/Digital 5kV Megger; 500, 1000, 2500, 5000V; 15 Tohms; Cat IV 600V.
Discontinued!
This product has been discontinued and is no longer available.
This is the direct replacement:
The new 5 kV insulation resistance testers from Megger
are designed specifically to assist you with the testing and
maintenance of high voltage electrical equipment. The
case is incredibly rugged and easy to carry, being made of
tough polypropylene and achieving an ingress protection
rating of IP65. In addition, the model number is marked on
both sides of the case for ease of identification in stores or
vehicles.
The instrument has a large easy to read backlit LCD display
making it equally suitable for use in both bright sunlight and
poorly lit environments. Information displayed includes
resistance, voltage, leakage current, capacitance, battery
status and time constant. In addition, the elapsed time of the
test is displayed constantly removing the need for separate
timers.
The instrument can test when being powered by the mains
or its internal rechargeable battery, a great benefit when site
conditions are unknown or long term testing is required.
The controls of the instrument are clear and unambiguous
and a "quick start" guide is included in the lid of the instrument removing the need to carry bulky manuals under site
conditions.
The instrument is fitted with a guard terminal to enhance
accuracy. The guard test lead is included as standard with
the instrument.
To further enhance the flexibility of the instrument the
MIT510/2 has the facility to set the test voltage in steps from
250 V to 5000 V avoiding the expense of several insulation
resistance testers to meet your application needs.
The IR tester is designed to meet the highest safety standards
and meets the requirements of EN61010. In addition, the
instrument measures the voltage at the terminals and if this
is above 50 V then the instrument will display the high voltage
warning and inhibit testing. At the end of the test the instrument
will automatically discharge the energy transferred to the
equipment during the test phase.
| Voltage Input Range | 85 - 260 V ± -10% rms 50 / 60Hz and DC |
| Battery Life | 8 hours continuous testing at 5 kV |
| Test Voltages | 250 V, 500 V, 1000 V, 2500 V, & 5000 V |
| Accuracy | ±5% to 1 T-ohm ±10% to 15 T-ohm |
| Guard | 2% error guarding 500 K-ohm leakage with 100 M-ohm load |
| Display Range | Digital Display: 10 K-ohm to 15 T-ohm Analog Display: 100 K-ohm to 1 T-ohm |
| Short Circuit / Charge Current | 3 mA |
| Capacitor Charge Time | 25 seconds per µF at 3 mA |
| Capacitor Discharge Time | 25 seconds per µF to discharge 5000V to 50V |
| Capacitance Measurement | 1 nF to 50 µF (Dependent on measurement voltage) |
| Capacitance Measurement Accuracy | ±5% ±5 nF |
| Voltage Output Accuracy | ±2% ±1 V of nominal test voltage at 100 M-ohm load ±25 V for test voltages less than 500 V |
| Current Measurement Range | ±0.01 nA to ±5 mA |
| Current Measurement Accuracy | ±5% ±0.2 nA at all voltages |
| Display | Analog / Digital 3 digits |
| Interference Rejection | 1 mA rms per kV test voltage, 2 mA rms maximum |
| Timer Range | Up to 99 minutes |
| Lead Set | Three Flexible silicon insulated leads with compact clamp |
| Ingress Protection | IP65 |
| Voltage Input Range | 85 - 260 V ± -10% rms 50 / 60Hz and DC |
| Battery Life | 8 hours continuous testing at 5 kV |
| Test Voltages | 250 V, 500 V, 1000 V, 2500 V, & 5000 V |
| Accuracy | ±5% to 1 T-ohm ±10% to 15 T-ohm |
| Guard | 2% error guarding 500 K-ohm leakage with 100 M-ohm load |
| Display Range | Digital Display: 10 K-ohm to 15 T-ohm Analog Display: 100 K-ohm to 1 T-ohm |
| Short Circuit / Charge Current | 3 mA |
| Capacitor Charge Time | 25 seconds per µF at 3 mA |
| Capacitor Discharge Time | 25 seconds per µF to discharge 5000V to 50V |
| Capacitance Measurement | 1 nF to 50 µF (Dependent on measurement voltage) |
| Capacitance Measurement Accuracy | ±5% ±5 nF |
| Voltage Output Accuracy | ±2% ±1 V of nominal test voltage at 100 M-ohm load ±25 V for test voltages less than 500 V |
| Current Measurement Range | ±0.01 nA to ±5 mA |
| Current Measurement Accuracy | ±5% ±0.2 nA at all voltages |
| Display | Analog / Digital 3 digits |
| Interference Rejection | 1 mA rms per kV test voltage, 2 mA rms maximum |
| Timer Range | Up to 99 minutes |
| Lead Set | Three Flexible silicon insulated leads with compact clamp |
| Ingress Protection | IP65 |