Hioki BT3554-52 KIT Battery Tester with magnetic strap, 3 mΩ to 3 Ω, 6 to 60 V

Model: BT3554-52 KIT

Hioki BT3554-52 KIT Battery Tester with magnetic strap, 3 mΩ to 3 Ω, 6 to 60 V

Model: BT3554-52 KIT

Designed for fast UPS and lead-acid battery diagnostics, the BT3554-50 offers complete internal resistance testing for accurate evaluation of battery deterioration and remaining life. Includes the L2020 Pin Type Lead with L-shaped, making it ideal for field use, while it streamlines maintenance with guided measurement and recording support.

Designed for fast UPS and lead-acid battery diagnostics, the BT3554-50 offers complete internal resistance testing for accurate evaluation of battery deterioration and remaining life. Includes the L2020 Pin Type Lead with L-shaped, making it ideal for field use, while it streamlines maintenance with guided measurement and recording support.

Your Price $3660.00 USD
Availability 2 to 3 Weeks
Quantity

Recommended Accessories


Hioki BT3554-52 KIT Offers

Features

  • Accuracy guaranteed for one year
  • Battery measurement can be performed while the battery is connected to its host device, without taking it offline
  • Measure and save data in as fast as 2 seconds, a 60% improvement from the legacy 3554
  • Instantaneously diagnose battery degradation (PASS, WARNING, FAIL) by measuring internal resistance and voltage*
    * The thresholds for determining the pass/fail condition of a battery depends on the specifications and standards of the battery manufacturer, battery type, capacity, etc. It is important and necessary to always conduct battery testing against the internal resistance and terminal voltage of a new or reference battery. In some cases, it may be difficult to determine the deterioration state of traditional open type (liquid) lead-acid or alkaline batteries which demonstrate smaller changes in internal resistance than sealed lead acid batteries.
  • Noise reduction technology improves noise resistance
  • Screen and audio * guidance simplifies measurement
    *Audio generated by Bluetooth®-connected device.
  • Measurement data is linked to site information and saved, reducing management man-hours
  • Easily transfer measurement data to your smartphone or tablet by using our free app GENNECT Cross * or to an Excel® file. (Wireless Adapter Z3210 is necessary)
    * Data can be downloaded to tablets and smartphones using Hioki’s dedicated free app "GENNECT Cross," available from the Google Play or App Store. (when using the Z3210)
  • New protector delivers better ergonomic hold and durability in the field

Accurately assess lead-acid battery deterioration using proprietary technology

The new Battery Tester BT3554-50 sets a new standard for UPS and lead-acid battery diagnostics. Since the battery’s internal resistance and voltage are measured using the impedance method, diagnostics can be performed while the battery is connected to its host device, without taking it offline. Proprietary noise reduction technology allows more accurate measurement, even in noisy environments.

Wireless support - Wireless communication capability for even greater convenience

Compatible with Wireless Adapter Z3210 (optional). It transfers measurements to your smartphone or tablet and allows you to quickly create reports with field photos and drawings.

Enjoy measurement guidance and easy data management functionality with the latest software

When the BT3554-50 is paired with a dedicated mobile app (GENNECT Cross), the mobile device will provide audio guidance announcing the next battery number to be measured. This feature helps prevent erroneous measurements. You can also set up measurement locations informations and battery numbers in advance to create profiles to which measurement data and diagnostic results will be linked. This capability simplifies data management, even when performing diagnostic work on large numbers of batteries.

Get Results in as Fast as 2 Seconds

Simply touch the test leads to the battery terminals to easily capture battery condition data with the Hioki BT3554-50 Battery Tester. Automatically save measurements results using the auto-hold or auto-memory function in just 2 seconds, a 60% reduction from the legacy product.

Generating comparative judgments based on a lead-acid battery’s internal resistance and voltage

By using its comparator function to simultaneously measure the internal resistance and voltage of a lead-acid, nickel-cadmium, or nickel-hydride battery, the BT3554-50 can generate comparative judgments quantifying degradation of the cell based on user-specified threshold values.

Furthermore, voltage sign detection facilitates instantaneous determination of whether batteries have been connected properly in newly installed UPS systems.

Saving data easily just by placing the leads in contact with a battery’s terminals

The BT3554-50 auto-hold function automatically holds measured values once they stabilize. The instrument’s auto-memory function, which automatically stores measured values resulting from the auto-hold function in its internal memory, further streamlines work tasks.

New leads for more convenient measurement in distribution panels and other confined locations

The Pin Type Lead L2020 with L-shaped tips is available as a new option. The design significantly improves ease of use when inspecting batteries installed in confined locations.

How to use Battery Testers: Observing Measurement Results Captured Wirelessly on a Mobile Device

Measured values captured by the Hioki BT3554-50 Battery Tester with Bluetooth wireless technology can be displayed and saved onto a mobile device wirelessly. (When using the Wireless Adapter Z3210). The results can also be used to create automatic reports. Simply install the free GENNECT Cross app onto your mobile device and connect to the Hioki BT3554-50. Reports created on your mobile device can even be e-mailed to the office to further increase work efficiency. Data uploaded by the Gennect Cross app can also be loaded into a PC to view the historical state of the specified battery as a graph.

Applications: Manage other UPS inspection data together

GENNECT can serve as a central repository for managing data from Hioki clamp meters and other instruments.

Example: UPS inspection

1.UPS system ACV measurement (CM4372, CM4374)

2.DCV measurement (CM4372, CM4374)

3.AC/DC current measurement (CM4372, CM4374)

4.Ripple current measurement (CM4002)

5.Battery degradation diagnostics (BT3554-50)

6.Measurement site photograph

Easily transfer measurement data to an Excel® file: Excel® Direct Input Function

Excel® Direct Input function allows you to input measurement values directly and automatically into an Excel® file once the instrument's auto-hold function is activated. (Wireless Adapter Z3210 is necessary)

Wall and shoulder straps let you work with both hands

If you’re measuring a number of batteries in a large area, use the included shoulder strap to carry the instrument with you while making measurements. Or if there are numerous batteries at a single location, use the Magnetic Strap Z5020 (sold separately) to hang the instrument on the wall while you work.

Applications

  • Management of Measurement Data for UPS Sites to Facilitate the Digital Transformation
  • Deterioration Judgment of Stationary Lead-Acid Batteries

Hioki BT3554-52 KIT Specifications

Resistance Measurement Range Accuracy: ±0.8% rdg ±6 dgt (3 mΩ range: ±1.0% rdg ±8 dgt)
Testing source frequency: 1 kHz ±30 Hz
With function for avoiding noise frequency enabled: 1 kHz ±80 Hz
Testing current: 160 mA (3m/30 mΩ range), 16 mA (300 mΩ range), 1.6 mA (3 Ω range)
Open terminal Voltage: 5 V peak
Voltage Measurement Range ±6 V (maximum display ±6.000 V, resolution: 1 mV) to ±60 V (maximum display ±60.00 V, resolution: 10 mV), 2 ranges
Accuracy: ±0.08% rdg ±6 dgt
Temperature Measurement Accuracy Measurement range: 14 to 140°F (-10 to 60°C)
Maximum display: 140.0°F (60.0°C)
Resolution 0.1°F (0.1°C)
Measurement accuracy*: ±1.8°F (±1.0°C)

*When using the Clip Type Lead with Temperature Sensor 9460
*When using the Temperature Probe 9451, add ± 0.9°F (±0.5°C) (cable length: 59.1" [1.5 m])
*When using the Temperature Probe 9451S, add ±0.9°F (±0.5°C) (cable length: 3.94" [0.1 m])
BT3554-50 standalone accuracy with simulated input: ±0.9°F (±0.5°C)
Absolute Maximum Input Voltage 60 V DC maximum (No AC input)
Measurement Time 100 ms
Response Time Approximately 1.6 seconds
Comparator Compares measured values with set threshold values to make judgments and reports them to the user
Judgment notification method: Results are displayed as shown below (segment) and beeping tones sound
When the Voltage value (high): Resistance value (low)= PASS, Resistance value (medium)= WARNING, Resistance value (high)= FAIL
When the Voltage value (low): Resistance value (low)= WARNING, Resistance value (medium)= WARNING, Resistance value (high)= FAIL
If the judgment result is WARNING or FAIL, the audio tone is accompanied by a red backlight
User-selectable voltage judgment method: ABS (absolute value judgment), POL (polarity judgment )
Savable settings: 200 tables
Memory Functionality Operation: Save, load, and delete measurement data, Save and delete profile information
Number of data sets: 6000
Memory architecture: 500 data sets per unit (12 units)
Saved data: Saved measurement data is linked to profile information

1. Measurement data: Data can be saved, loaded, and deleted by operating the instrument.
-1. Date and time
-2. Resistance value, voltage value, and temperature
-3. Comparator threshold value and judgment result

2. Profile information: Profile information can be saved, loaded, and deleted using a supported application (GENNECT Cross or GENNECT One).
-1. Profile numbers: 1 to 100 (Data (2), (3), and (4) below are saved for each profile number)
-2. Location: User-defined comment such as location of UPS
-3. Device information: User-defined comment such as UPS management number
-4. Battery number: 1 to 500 (start number, end number)
Measurement Navigator Operation: Announces the next battery number to be measured via a screen display and audio guidance
Audio output is generated by a connected mobile device when using the Z3210 and a supported application (GENNECT Cross)
Preparations: Profile information that's been registered with a supported application (GENNECT Cross or GENNECT One) must be transferred to the instrument
Communication Interface USB
Bluetooth® wireless communications (when Z3210 installed)
Other Functions Temperature measurement (-10 to 60°C)
Zero-adjustment
Hold
Auto-hold
Auto-memory
Auto-power-save
Clock
Power Supply LR6 (size AA) alkaline battery ×8
Rated supply voltage: 1.5 V DC × 8
(Nickel metal hydride batteries may be used. However, the battery life display is not supported in this configuration.)
Continuous operating time: Approximately. 8.3 hours (without Z3210 installed)
Approximately 8.2 hours (with Z3210 installed and wireless communications active)
Dimensions 7.83 x 5.2 x 2.39" (199 x 132 x 60.6 mm), with protector
Weight 960 g (33.9 oz), including batteries and protector

What's included with the Hioki BT3554-52 KIT

  • Battery Tester
  • Pin Type Lead L2020
  • Protector Z5041
  • Fuse Set Z5050
  • Adjustment Board
  • Neck Strap
  • USB Cable
  • Carrying Case C1014
  • 8 x AA alkaline Battery (LR6)
  • Application Software CD (GENNECT One)
  • User Manual

Click on a category to view a selection of compatible accessories with the Hioki BT3554-52 KIT Battery Tester with magnetic strap, 3 mΩ to 3 Ω, 6 to 60 V.

Hioki 9451 Temperature Probe, 59" 9451
The temperature sensor is a 59" (1.5 m) long probe designed for use with BT3554 battery testers. This sensor provides accurate temperature readings, ensuring optimal battery testing conditions. Its compact size makes it easy to integrate into various testing setups, enhancing the versatility and precision of battery diagnostics. 




Hioki 9451-01 Temperature Probe, 3.9" 9451-01
The temperature sensor is a 3.9" (10 cm) long probe designed for use with BT3554 battery testers. This sensor provides accurate temperature readings, ensuring optimal battery testing conditions. Its compact size makes it easy to integrate into various testing setups, enhancing the versatility and precision of battery diagnostics. 




Hioki C1014 Carrying Case, 9.84 x 10.24 x 4.72" C1014
The C1014 is a hard-shell carrying case designed to transport and protect the BT3554 Battery Tester and its accessories. With outer dimensions of 9.84 x 10.24 x 4.72" (250 x 260 x 120 mm) and a weight of approximately 3.1 lbs (1.4 kg), the case features a custom foam insert that securely holds the instrument in place. Its robust design ensures reliable protection during storage or transport. The instrument and accessories are not included.




Ask a question about Hioki BT3554-52 KIT Battery Tester with magnetic strap, 3 mΩ to 3 Ω, 6 to 60 V

Customer Reviews for the Hioki BT3554-52 KIT

Hioki BT3554-52 KIT Offers

Features

  • Accuracy guaranteed for one year
  • Battery measurement can be performed while the battery is connected to its host device, without taking it offline
  • Measure and save data in as fast as 2 seconds, a 60% improvement from the legacy 3554
  • Instantaneously diagnose battery degradation (PASS, WARNING, FAIL) by measuring internal resistance and voltage*
    * The thresholds for determining the pass/fail condition of a battery depends on the specifications and standards of the battery manufacturer, battery type, capacity, etc. It is important and necessary to always conduct battery testing against the internal resistance and terminal voltage of a new or reference battery. In some cases, it may be difficult to determine the deterioration state of traditional open type (liquid) lead-acid or alkaline batteries which demonstrate smaller changes in internal resistance than sealed lead acid batteries.
  • Noise reduction technology improves noise resistance
  • Screen and audio * guidance simplifies measurement
    *Audio generated by Bluetooth®-connected device.
  • Measurement data is linked to site information and saved, reducing management man-hours
  • Easily transfer measurement data to your smartphone or tablet by using our free app GENNECT Cross * or to an Excel® file. (Wireless Adapter Z3210 is necessary)
    * Data can be downloaded to tablets and smartphones using Hioki’s dedicated free app "GENNECT Cross," available from the Google Play or App Store. (when using the Z3210)
  • New protector delivers better ergonomic hold and durability in the field

Accurately assess lead-acid battery deterioration using proprietary technology

The new Battery Tester BT3554-50 sets a new standard for UPS and lead-acid battery diagnostics. Since the battery’s internal resistance and voltage are measured using the impedance method, diagnostics can be performed while the battery is connected to its host device, without taking it offline. Proprietary noise reduction technology allows more accurate measurement, even in noisy environments.

Wireless support - Wireless communication capability for even greater convenience

Compatible with Wireless Adapter Z3210 (optional). It transfers measurements to your smartphone or tablet and allows you to quickly create reports with field photos and drawings.

Enjoy measurement guidance and easy data management functionality with the latest software

When the BT3554-50 is paired with a dedicated mobile app (GENNECT Cross), the mobile device will provide audio guidance announcing the next battery number to be measured. This feature helps prevent erroneous measurements. You can also set up measurement locations informations and battery numbers in advance to create profiles to which measurement data and diagnostic results will be linked. This capability simplifies data management, even when performing diagnostic work on large numbers of batteries.

Get Results in as Fast as 2 Seconds

Simply touch the test leads to the battery terminals to easily capture battery condition data with the Hioki BT3554-50 Battery Tester. Automatically save measurements results using the auto-hold or auto-memory function in just 2 seconds, a 60% reduction from the legacy product.

Generating comparative judgments based on a lead-acid battery’s internal resistance and voltage

By using its comparator function to simultaneously measure the internal resistance and voltage of a lead-acid, nickel-cadmium, or nickel-hydride battery, the BT3554-50 can generate comparative judgments quantifying degradation of the cell based on user-specified threshold values.

Furthermore, voltage sign detection facilitates instantaneous determination of whether batteries have been connected properly in newly installed UPS systems.

Saving data easily just by placing the leads in contact with a battery’s terminals

The BT3554-50 auto-hold function automatically holds measured values once they stabilize. The instrument’s auto-memory function, which automatically stores measured values resulting from the auto-hold function in its internal memory, further streamlines work tasks.

New leads for more convenient measurement in distribution panels and other confined locations

The Pin Type Lead L2020 with L-shaped tips is available as a new option. The design significantly improves ease of use when inspecting batteries installed in confined locations.

How to use Battery Testers: Observing Measurement Results Captured Wirelessly on a Mobile Device

Measured values captured by the Hioki BT3554-50 Battery Tester with Bluetooth wireless technology can be displayed and saved onto a mobile device wirelessly. (When using the Wireless Adapter Z3210). The results can also be used to create automatic reports. Simply install the free GENNECT Cross app onto your mobile device and connect to the Hioki BT3554-50. Reports created on your mobile device can even be e-mailed to the office to further increase work efficiency. Data uploaded by the Gennect Cross app can also be loaded into a PC to view the historical state of the specified battery as a graph.

Applications: Manage other UPS inspection data together

GENNECT can serve as a central repository for managing data from Hioki clamp meters and other instruments.

Example: UPS inspection

1.UPS system ACV measurement (CM4372, CM4374)

2.DCV measurement (CM4372, CM4374)

3.AC/DC current measurement (CM4372, CM4374)

4.Ripple current measurement (CM4002)

5.Battery degradation diagnostics (BT3554-50)

6.Measurement site photograph

Easily transfer measurement data to an Excel® file: Excel® Direct Input Function

Excel® Direct Input function allows you to input measurement values directly and automatically into an Excel® file once the instrument's auto-hold function is activated. (Wireless Adapter Z3210 is necessary)

Wall and shoulder straps let you work with both hands

If you’re measuring a number of batteries in a large area, use the included shoulder strap to carry the instrument with you while making measurements. Or if there are numerous batteries at a single location, use the Magnetic Strap Z5020 (sold separately) to hang the instrument on the wall while you work.

Applications

  • Management of Measurement Data for UPS Sites to Facilitate the Digital Transformation
  • Deterioration Judgment of Stationary Lead-Acid Batteries

Hioki BT3554-52 KIT Specifications

Resistance Measurement Range Accuracy: ±0.8% rdg ±6 dgt (3 mΩ range: ±1.0% rdg ±8 dgt)
Testing source frequency: 1 kHz ±30 Hz
With function for avoiding noise frequency enabled: 1 kHz ±80 Hz
Testing current: 160 mA (3m/30 mΩ range), 16 mA (300 mΩ range), 1.6 mA (3 Ω range)
Open terminal Voltage: 5 V peak
Voltage Measurement Range ±6 V (maximum display ±6.000 V, resolution: 1 mV) to ±60 V (maximum display ±60.00 V, resolution: 10 mV), 2 ranges
Accuracy: ±0.08% rdg ±6 dgt
Temperature Measurement Accuracy Measurement range: 14 to 140°F (-10 to 60°C)
Maximum display: 140.0°F (60.0°C)
Resolution 0.1°F (0.1°C)
Measurement accuracy*: ±1.8°F (±1.0°C)

*When using the Clip Type Lead with Temperature Sensor 9460
*When using the Temperature Probe 9451, add ± 0.9°F (±0.5°C) (cable length: 59.1" [1.5 m])
*When using the Temperature Probe 9451S, add ±0.9°F (±0.5°C) (cable length: 3.94" [0.1 m])
BT3554-50 standalone accuracy with simulated input: ±0.9°F (±0.5°C)
Absolute Maximum Input Voltage 60 V DC maximum (No AC input)
Measurement Time 100 ms
Response Time Approximately 1.6 seconds
Comparator Compares measured values with set threshold values to make judgments and reports them to the user
Judgment notification method: Results are displayed as shown below (segment) and beeping tones sound
When the Voltage value (high): Resistance value (low)= PASS, Resistance value (medium)= WARNING, Resistance value (high)= FAIL
When the Voltage value (low): Resistance value (low)= WARNING, Resistance value (medium)= WARNING, Resistance value (high)= FAIL
If the judgment result is WARNING or FAIL, the audio tone is accompanied by a red backlight
User-selectable voltage judgment method: ABS (absolute value judgment), POL (polarity judgment )
Savable settings: 200 tables
Memory Functionality Operation: Save, load, and delete measurement data, Save and delete profile information
Number of data sets: 6000
Memory architecture: 500 data sets per unit (12 units)
Saved data: Saved measurement data is linked to profile information

1. Measurement data: Data can be saved, loaded, and deleted by operating the instrument.
-1. Date and time
-2. Resistance value, voltage value, and temperature
-3. Comparator threshold value and judgment result

2. Profile information: Profile information can be saved, loaded, and deleted using a supported application (GENNECT Cross or GENNECT One).
-1. Profile numbers: 1 to 100 (Data (2), (3), and (4) below are saved for each profile number)
-2. Location: User-defined comment such as location of UPS
-3. Device information: User-defined comment such as UPS management number
-4. Battery number: 1 to 500 (start number, end number)
Measurement Navigator Operation: Announces the next battery number to be measured via a screen display and audio guidance
Audio output is generated by a connected mobile device when using the Z3210 and a supported application (GENNECT Cross)
Preparations: Profile information that's been registered with a supported application (GENNECT Cross or GENNECT One) must be transferred to the instrument
Communication Interface USB
Bluetooth® wireless communications (when Z3210 installed)
Other Functions Temperature measurement (-10 to 60°C)
Zero-adjustment
Hold
Auto-hold
Auto-memory
Auto-power-save
Clock
Power Supply LR6 (size AA) alkaline battery ×8
Rated supply voltage: 1.5 V DC × 8
(Nickel metal hydride batteries may be used. However, the battery life display is not supported in this configuration.)
Continuous operating time: Approximately. 8.3 hours (without Z3210 installed)
Approximately 8.2 hours (with Z3210 installed and wireless communications active)
Dimensions 7.83 x 5.2 x 2.39" (199 x 132 x 60.6 mm), with protector
Weight 960 g (33.9 oz), including batteries and protector

What's included with the Hioki BT3554-52 KIT

  • Battery Tester
  • Pin Type Lead L2020
  • Protector Z5041
  • Fuse Set Z5050
  • Adjustment Board
  • Neck Strap
  • USB Cable
  • Carrying Case C1014
  • 8 x AA alkaline Battery (LR6)
  • Application Software CD (GENNECT One)
  • User Manual

Click on a category to view a selection of compatible accessories with the Hioki BT3554-52 KIT Battery Tester with magnetic strap, 3 mΩ to 3 Ω, 6 to 60 V.

Hioki 9451 Temperature Probe, 59" 9451
The temperature sensor is a 59" (1.5 m) long probe designed for use with BT3554 battery testers. This sensor provides accurate temperature readings, ensuring optimal battery testing conditions. Its compact size makes it easy to integrate into various testing setups, enhancing the versatility and precision of battery diagnostics. 




Hioki 9451-01 Temperature Probe, 3.9" 9451-01
The temperature sensor is a 3.9" (10 cm) long probe designed for use with BT3554 battery testers. This sensor provides accurate temperature readings, ensuring optimal battery testing conditions. Its compact size makes it easy to integrate into various testing setups, enhancing the versatility and precision of battery diagnostics. 




Hioki C1014 Carrying Case, 9.84 x 10.24 x 4.72" C1014
The C1014 is a hard-shell carrying case designed to transport and protect the BT3554 Battery Tester and its accessories. With outer dimensions of 9.84 x 10.24 x 4.72" (250 x 260 x 120 mm) and a weight of approximately 3.1 lbs (1.4 kg), the case features a custom foam insert that securely holds the instrument in place. Its robust design ensures reliable protection during storage or transport. The instrument and accessories are not included.




Ask a question about Hioki BT3554-52 KIT Battery Tester with magnetic strap, 3 mΩ to 3 Ω, 6 to 60 V

Customer Reviews for the Hioki BT3554-52 KIT

More Hioki Products