3 in 1 instrument possessing a digital display gauge, control relay switches, and a transmitter with current output. Is ideal for pressure, velocity and flow applications, achieving a 0.5% full scale accuracy on ranges from 0.25 to 100"w.c. Two SPDT control relays with adjustable dead bands are provided along with a scalable 4-20 mA process output.
3 in 1 instrument possessing a digital display gauge, control relay switches, and a transmitter with current output. Is ideal for pressure, velocity and flow applications, achieving a 0.5% full scale accuracy on ranges from 0.25 to 100"w.c. Two SPDT control relays with adjustable dead bands are provided along with a scalable 4-20 mA process output.
Features
| Service | Air and non-combustible, non-conducting compatible gases |
| Wetted Materials | Consult factory |
| Housing Material | ABS plastic, UL approved 94-V-0 |
| Accuracy | ±0.5% at 77°F (25°C) including hysteresis and repeatability |
| Stability | ≤±1% per year |
| Temperature Limits | 32 to 140°F (0 to 60°C) |
| Compensated Temperature Limits | 32 to 140°F (0 to 60°C) |
| Thermal Effects | 0.020%/°F (0.036/°C) from 77°F (25°C) |
| Low Voltage Power | 24 VAC ±20% |
| High Voltage Power | 100 to 240 VAC, 132 to 240 VDC - 7 VA max |
| Output Signal | 4 to 20 mA DC into 900 ohms max |
| Response Time | 250 ms |
| Display | 4 digit LCD 0.4" height. LED indicators for set point and alarm status |
| Electrical Connections | Screw terminals |
| Process Connections | Compression fitting for use with 3⁄16" OD x ⅛" ID tubing |
| Enclosure Rating | Face designed to meet NEMA 4X (IP66) |
| Mounting Orientation | Mount unit in horizontal plane |
| Service | Air and non-combustible, non-conducting compatible gases |
| Wetted Materials | Consult factory |
| Housing Material | ABS plastic, UL approved 94-V-0 |
| Accuracy | ±0.5% at 77°F (25°C) including hysteresis and repeatability |
| Stability | ≤±1% per year |
| Temperature Limits | 32 to 140°F (0 to 60°C) |
| Compensated Temperature Limits | 32 to 140°F (0 to 60°C) |
| Thermal Effects | 0.020%/°F (0.036/°C) from 77°F (25°C) |
| Low Voltage Power | 24 VAC ±20% |
| High Voltage Power | 100 to 240 VAC, 132 to 240 VDC - 7 VA max |
| Output Signal | 4 to 20 mA DC into 900 ohms max |
| Response Time | 250 ms |
| Display | 4 digit LCD 0.4" height. LED indicators for set point and alarm status |
| Electrical Connections | Screw terminals |
| Process Connections | Compression fitting for use with 3⁄16" OD x ⅛" ID tubing |
| Enclosure Rating | Face designed to meet NEMA 4X (IP66) |
| Mounting Orientation | Mount unit in horizontal plane |