Capable of measuring low pressures with a ±1% accuracy - ideally suited for proper building pressurization and air flow control. Transmitters can withstand up to 10 psig overpressure with no damage to the unit.
Capable of measuring low pressures with a ±1% accuracy - ideally suited for proper building pressurization and air flow control. Transmitters can withstand up to 10 psig overpressure with no damage to the unit.
Specifications
Service: Air and non-conductive gases.
Accuracy: ±1% of full scale (RSS), (includes non-linearity, hysteresis, and non-repeatability).
Temperature Limits: Operating: 0 to 150°F (-18 to 65°C),
Storage: -40 to 185°F (-40 to 85°C).
Pressure Limits: 10 psig (0.69 bar)
Compensated Temperature Range: 0 to 150°F (-18 to 65°C
Thermal Effects: 0.033% FS/°F (0.18% FS/°C)
Supply Voltage: 12-30 VDC. Output: 4 to 20 mA, 2-wire
Zero and Span Adjustment: ±1 mA, non-interactive
Response Time: <60 msec
Loop Resistance: 0-800 ohms
Electrical Connection: Terminal strip
Pressure Connection: 3/16" O.D. fitting for 1/4" I.D. tubing
Housing: Fire retardant glass filled polyester
Weight: 3 oz (85 g)
Agency Approval: CE