Delivers the best refrigerant leak detection available, with industry-leading MDL of 1ppm for halogenated gases, the fastest sampling frequency and the widest range of refrigerants accurately detected.
Delivers the best refrigerant leak detection available, with industry-leading MDL of 1ppm for halogenated gases, the fastest sampling frequency and the widest range of refrigerants accurately detected.
The Multi-Zone enhances effective refrigerant management, detecting leaks early to enable cost savings by reducing refrigerant recharge, enhancing energy efficiency and reducing risk of refrigeration failure and produce loss. A variety of communication interfaces are available including Modbus, BACnet and LonWorks, allowing easy integration into BMS/BAS systems and remote monitoring solutions.
Features
| Type | 8 point sampling system using IR sensor technology | 
| Gases | Refrigerants: CFCs, HFCs, HCFCs, HFOs Natural Refrigerants: Ammonia, Carbon Dioxide  | 
	
| Measuring Range | Refrigerants: 0 to 10,000 ppm Ammonia: 25 to 10,000 ppm Carbon Dioxide: 300 to 8,000 ppm  | 
	
| Sensitivity | Refrigerants: 1 ppm Ammonia: 25 ppm Carbon Dioxide: 10 ppm  | 
	
| Sampling Distance | 0 to 1,200 ft. (0 to 365 m) for each sampling point | 
| Display | Backlit, Graphic LCD 160 x 128 Pixel; Three Status LEDs | 
| Output | Digital Modbus® RTU via RS 485 Analog 4 to 20 mA (Optional)  | 
	
| Power Supply | 100 to 240 VAC, 50 / 60 Hz | 
| Relay | 3 Alarm Relays, 1 Fault Relay, SPDT - Rating 5 A @ 250 VAC, Resistive Load | 
| Ambient Conditions | Temperature: 32 to +122 °F (0 to +50 °C) Humidity: 5 to 90 %RH, Non Condensing Altitude: 0 to 6,560 ft (2,000 m)  | 
	
| Enclosure | Powder-Coated Aluminum | 
| Size | Approx. 13.7 x 12.3 x 5" (350 x 315 x 130 mm) | 
| Weight | Approx. 15 lbs. (6.8 kg) | 
| Approvals | CE, UL, CSA, EN 61010-1, EN 61326, EN 14624 | 
| Type | 8 point sampling system using IR sensor technology | 
| Gases | Refrigerants: CFCs, HFCs, HCFCs, HFOs Natural Refrigerants: Ammonia, Carbon Dioxide  | 
	
| Measuring Range | Refrigerants: 0 to 10,000 ppm Ammonia: 25 to 10,000 ppm Carbon Dioxide: 300 to 8,000 ppm  | 
	
| Sensitivity | Refrigerants: 1 ppm Ammonia: 25 ppm Carbon Dioxide: 10 ppm  | 
	
| Sampling Distance | 0 to 1,200 ft. (0 to 365 m) for each sampling point | 
| Display | Backlit, Graphic LCD 160 x 128 Pixel; Three Status LEDs | 
| Output | Digital Modbus® RTU via RS 485 Analog 4 to 20 mA (Optional)  | 
	
| Power Supply | 100 to 240 VAC, 50 / 60 Hz | 
| Relay | 3 Alarm Relays, 1 Fault Relay, SPDT - Rating 5 A @ 250 VAC, Resistive Load | 
| Ambient Conditions | Temperature: 32 to +122 °F (0 to +50 °C) Humidity: 5 to 90 %RH, Non Condensing Altitude: 0 to 6,560 ft (2,000 m)  | 
	
| Enclosure | Powder-Coated Aluminum | 
| Size | Approx. 13.7 x 12.3 x 5" (350 x 315 x 130 mm) | 
| Weight | Approx. 15 lbs. (6.8 kg) | 
| Approvals | CE, UL, CSA, EN 61010-1, EN 61326, EN 14624 |