Features a flexible Rogowski coil and an electronic module, the sensor permits measurements on conductors where standard clamp-on probes cannot be used. Can be installed in tight spaces, around cable bundles, bus bars, or even wrapped around irregular shapes.
Features a flexible Rogowski coil and an electronic module, the sensor permits measurements on conductors where standard clamp-on probes cannot be used. Can be installed in tight spaces, around cable bundles, bus bars, or even wrapped around irregular shapes.
Features
Nominal Range | 3; 30; 300; 3000 AAC |
Measurement Range | 3 A Range: 0.5 to 3 AAC 30 A Range: 2 to 30 AAC 300 A Range: 5 to 300 AAC 3000 A Range: 50 to 3000 AAC |
Transformation Ratio | Voltage output |
Output Signal | 3 A Range: 1 V/A (1 mV/mA) (3 VAC @ 3 A) 30 A Range: 100 mV/A (3 VAC @ 30 A) 300 A Range: 10 mV/A (3 VAC @ 300 A) 3000 A Range: 1 mV/A (3 VAC @ 3000 A) |
Accuracy | 3 A, 30 A Range: ≤1% of reading ±40 mA 300 A, 3000 A Range: ≤1.5% of reading + 40mA (l≤10% Inom) ≤1% of Reading + 40 mA (l≥10% Inom) |
Phase Shift | ≤1° (0.5° typical) |
Overload | 3 A Range: 4.5 A 30 A Range: 45 A 300 A Range: 450 A 3000 A Range: 4500 A |
Load Impedance | ≥1 MΩ |
Work Voltage | 600 Vrms (CAT IV) 1000 Vrms (CAT III) |
Battery | Type: 2 x 1.5 V AA batteries or LR6 alkaline, +5VDC with type B micro-USB Life: 300 hours typical; approximately 1800 10-minute measurements |
Output Termination | 1.6' (0.5m) lead with two 4 mm safety banana plugs |
Electrical | IEC 61010-2-32 type B, 1000V CAT III, 600V CAT IV, Pollution Degree 2 |
Electromagnetic Compatibility | IEC 61326-1 |
Protection | IP54 (electronic unit), IP67 (flexible sensor) |
Nominal Range | 3; 30; 300; 3000 AAC |
Measurement Range | 3 A Range: 0.5 to 3 AAC 30 A Range: 2 to 30 AAC 300 A Range: 5 to 300 AAC 3000 A Range: 50 to 3000 AAC |
Transformation Ratio | Voltage output |
Output Signal | 3 A Range: 1 V/A (1 mV/mA) (3 VAC @ 3 A) 30 A Range: 100 mV/A (3 VAC @ 30 A) 300 A Range: 10 mV/A (3 VAC @ 300 A) 3000 A Range: 1 mV/A (3 VAC @ 3000 A) |
Accuracy | 3 A, 30 A Range: ≤1% of reading ±40 mA 300 A, 3000 A Range: ≤1.5% of reading + 40mA (l≤10% Inom) ≤1% of Reading + 40 mA (l≥10% Inom) |
Phase Shift | ≤1° (0.5° typical) |
Overload | 3 A Range: 4.5 A 30 A Range: 45 A 300 A Range: 450 A 3000 A Range: 4500 A |
Load Impedance | ≥1 MΩ |
Work Voltage | 600 Vrms (CAT IV) 1000 Vrms (CAT III) |
Battery | Type: 2 x 1.5 V AA batteries or LR6 alkaline, +5VDC with type B micro-USB Life: 300 hours typical; approximately 1800 10-minute measurements |
Output Termination | 1.6' (0.5m) lead with two 4 mm safety banana plugs |
Electrical | IEC 61010-2-32 type B, 1000V CAT III, 600V CAT IV, Pollution Degree 2 |
Electromagnetic Compatibility | IEC 61326-1 |
Protection | IP54 (electronic unit), IP67 (flexible sensor) |