Hioki 9694 Clamp On Sensor 5A AC (3169 and 3196)
Clamp-on Sensors for the POWER QUALITY ANALYZER 3196 and CLAMP ON POWER HiTESTER 3169
For input of 5A CT, select our Model 9694, This sensor is are designed with a safety barrier to protect the user from being in direct contact with live conductors and completely meet all CE marking requirements.
Basic Specifications
- Rated input current 5 A AC
- Rated output current 50 mV AC
- Accuracy (at 45 to 66 Hz) Amplitude: ±0.3 % rdg. ±0.02 % f.s. , Full scale (f.s.) is the 3196 range value,
Phase: ±2° or less
- Frequency characteristics 66 Hz to 5 kHz (±1 % or less from accuracy)
- Max. allowable input continuous 50 A rms (45 to 66 Hz)
- Max. circuit voltage 300 V AC rms (insulated wire)
- Core jaw dia. Ø15 mm(0.59 in)
- Dimensions, mass 46 mm(1.81 in)W × 135 mm(5.31 in)H × 21 mm(0.83 in)D, 230 g (8.1 oz), cord length: 3 m(9.84 ft)