The AmpFlex® is a flexible AC current probe composed of a flexible sensor and an electronic module. The flexible sensor permits measurements on conductors where standard clamp-on probes cannot be used. Measurement range is 5 to 6000A. Output signal is 1mV/A and 0.1mV/A. Sensor length is 36".

Applications:
  • Measuring wide bus bars
  • Measuring crowded circuit breaker panels
  • Measuring around large cable bundles
  • Measuring in any traditional application
  • Measuring around irregular shapes

Electrical Specifications
Measurement Range 5 to 6000A
Output Signal 1mV/A & 0.1mV/A
Accuracy 1% of Reading
Phase Shift @ 50/60Hz 0.5°
Frequency Range 10 to 20,000Hz (intentionally limited for optimum performance)
Residual Noise 500mA
Working Voltage 1000Vrms max.
Influence of Frequency Add 1% to the reference
Influence of Adjacent Conductor <2%
Influence of Conductor Position in Jaw <4%
Mechanical Specifications
Output Two 4mm safety banana jacks, standard 3/4" (19mm) spacing
Battery 9V Alkaline
Low Battery Green LED Off when ³ 7V
Overload Indication Red LED indicates input greater than selected range
Battery Life 150 hours typical (continuous use)
Sensor Dimensions 36"
Electronic Module Dimensions 4.9 x 2.5 x 1.1" (124 x 64 x 28mm)
Cable Length 6.5ft (2m)
Drop Test 1.0m on 38mm of oak or concrete. Test according to IEC1010
Vibration Test per IEC 68-2-6, Frequency Range: 10Hz to 55Hz, Amplitude: 0.15mm
Mechanical Shock 100G, Test per IEC 68-2-32
Environmental Specification
Case Protection Sensor: IP65 per IEC529; Electronic Module: IP40
Operating Temperature 14 to 131°F (-10°C to +55°C)
Storage Temperature -40 to 158°F (40°C to +70°C)
Influence of Temperature Sensor: -10°C to 100°C: <0.5% per 10°C; Module: -10°C to 55°C: <0.5% per 10°C
Operative Relative Humidity 10 - 30°C 85 ±5% RH without condensation; 40 - 50°C 45 ±5% RH (without condensation)
Altitude Operating: 0 to 2000m; non-operating: 0 to 12000m
Safety Reference Specifications
Safety Ratings EN 61010, 1000V, Cat. III, Pollution Degree 2